- Up to 10 limit value detectors can be connected per TSZ 0400 Door Control Unit
- All standard, permitted 24 V automatic door controls can be activated
- Up to 3 TSZ 0400 Door Control Units can be linked together
- The detector group is monitored for interruption, short circuit and triggered alarms
BOSCH - TSZ 0400 DOOR COTROL UNIT
Operating voltage: 230 V AC, +/-15%
Mains frequency: 50 Hz
Current consumption: 50 mA approx.
Permitted contact load ;
Door control device and buzzer: 24 V DC / max. 0.8 A
Potential-free change-over: 30 V DC / max. 1.0 A
Standby line voltage: 22 V approx.
Standby line current: 4 mA
End of line resistor RE (when connected to Bosch detectors): 3k92
Maximum line resistance: 100 Ω
Fault emission: DIN EN 61000-6-3
Fault influence: DIN EN 50082-1 DIN EN 50082-2 DIN EN 50130-4 VdS 2110, prEN 54-2
Climatic test: DIN IEC 68-2-3
NSR 73/23 EWG device safety: DIN EN 60950 A4
Protection class as per EN 60529: IP 42
Permitted ambient temperature: 0 °C . . . 40 °C
Permitted storage temperature: -40 °C . . . +70 °C
Connectable detectors: 10 max.
Housing material: Polystyrol (PS)
Housing color: Grey, RAL 9002
Weight: 1,500 g approx.